オンラインチャット

+8615317905991

Circuit Breaker Tripping Characteristics Comprehensive Test System

商品番号:

伝言を残す

=

Circuit Breaker Tripping Characteristics Comprehensive Test System

伝言を残す

=
製品説明

The LS-B60 circuit breaker tripping characteristic comprehensive test system adopts the principle of low voltage and high current output, uses the built-in high current isolation transformer to output current, sets the current size through the touch screen to control the constant current source to adjust the output current size, and has the function of automatically stabilizing the current. The test time is set through the touch screen display and compared with the test tripping time to judge the quality of the circuit breaker.

LS-B60 can perform a delayed tripping characteristic test on the circuit breaker, that is, apply 1.13 times, 1.45 times, and 2.55 times the rated current to test whether it trips within the specified time; it can also perform an instantaneous tripping characteristic test on the circuit breaker, that is, apply 3~10 times the rated current to test whether it trips within the specified time. It is used for delayed tripping characteristic tests, instantaneous tripping characteristic tests, and temperature rise tests of molded case circuit breakers and small circuit breakers to assess whether the circuit breaker tripping characteristics meet standard requirements.

Standards:
IEC 60947-1:2011《Low-votage switchgear and controlgear Part1:General rules》 Clause 7.2.1
IEC 60947-2:2006《Low-votage switchgear and controlgear Part1:Circuit breakers》Clause 4.7
IEC 60898-1:2002
IEC 60009-1:2012

Specifications:

Electrical Control MethodPLC intelligent integrated control, human-machine touch interface operation
Test ChamberThe test chamber is combined with the test machine, with a built-in delay position and an instantaneous position, and is arranged on the back panel in a terminal manner to meet the 1-4P circuit breaker test. When the temperature inside the chamber is too low, it can be heated, ranging from room temperature to 50 degrees, with a temperature resolution of 0.1 degrees and a temperature stability of ±1 degree, providing a reliable and safe environment for circuit breaker testing.
Test Items• Small/molded case time-delay tripping characteristics: 1.13 times, 1.45 times, 2.55 times the current
• Instantaneous tripping characteristics: 3~10 times the current
• Temperature rise test
Time-delay Tripping Test
出力電流AC10~350A
出力電圧0~5V
Output Current Path1-way output, multi-P circuit breaker contacts are tested by connecting several switches in series
Test Sample Range3~125A
Current Output WaveformSine wave (correction equipment current waveform distortion is no more than 5%, system error is no more than 3%)
Current Control MethodAutomatic adjustment, current setting on touch screen
Current Accuracy0.5 Class
Voltage Accuracy0.5 Class
Transformer Ratio400/5A
Testing Time1~9999H 59M  59s
Testing ProcessAfter applying 1.13 times the current, it will automatically rise to 1.45 times the current in 5 seconds
FixtureAdopting terminal mode, one delay position, one instantaneous position; meeting 1-4P circuit breaker
Instantaneous Tripping Test
出力電流AC100~1500A
Output Voltage Number1
Current Accuracy0.5 Class
Resolution1A
Instantaneous Test Time≤0.2s
Action Time Upper Limit Setting1~200ms
Action Time Lower Limit Setting1~200ms
Test Station1
Timekeeping1~9999ms
Protection FunctionShort circuit protection, overload protection, leakage protection
Temperature Rise Test
Purpose of the TestWhen the circuit breaker is tested under normal working conditions and specified conditions, the temperature rise of its components shall not exceed the limit values ​​specified in Table 6, and the circuit breaker shall not be damaged to affect its function or safety of use.
Test CurrentAC10-350A
Temperature Measurement Channel12 channels, temperature resolution 0.1 degrees
正確さ0.2 Class
Measurement and Control Speed0.1 seconds per channel
Temperature Measurement Range0~200℃
Thermocouple ModelT type